Central mains and system protection in accordance with VDE-AR-N 4105:2015-11 with motor-driven tie switch.
Product features:
• Installed NA monitor: TeleNA003-M64
• Max. apparent power of the generation system: 172.5 kVA
• Max. active power of the generating system: 155.0 kVA
• Max. rated current: 250 A
• AC grid: 230/400 V, 3-phase
• Permitted grid types Grid connection: TN-S, TT
• Max. cable cross-section: 35 – 150 mm²
• Protection class: IP 54
• Dimensions: 720 x 360 x 230 mm (H x B x T)
• Weight: approx. 15.4 kg