Product information "BYD HVM+ 8.3 + PLENTICORE PLUS 8.5 G2"
The PLENTICOINs required to enable power and functions must be ordered separately.
Combination with components from the previous HVS series is not possible.
The new BYD Energy app with the latest firmware (from V1.28.0) is required for commissioning.
The RJ45 terminating connector for the data bus included in the scope of delivery must be pre-assembled on site. To do this, a wire jumper must be inserted and crimped between pins 1 and 6 (view from above onto the flat connector side with the pin contact surfaces, cable entry facing down, pins ascending from left to right). An actual resistor is not required.
HVS+/HVM+ and Kostal: approved by the manufacturers on both sides
Wichtige technische Daten
| Dangerous goods transportation category | 2 |
|---|---|
| Dangerous goods description | LITHIUM ION BATTERIES |
| Tunnel restriction code | (E) |
| Classification code | M4 |
| Dangerous goods class | 9 |
| Dangerous goods packaging type | 4G |
| UN No. | 3480 |
| Dangerous goods Weight (net) (kg) | 123.900 |
Downloads
-
Battery-Box HVM+ 2.76 kWh0161505
-
SMART ENERGY METER G20151118
-
Plenticore Plus 8.5 G2 Hybrid IV0152314
-
B-Box BCU + Base (HVB/HVS+/HVM+)0161507
-
SMART ENERGY METER G20151118
-
Plenticore Plus 8.5 G2 Hybrid IV0152314
Technical details
| Topology | transformerless |
|---|---|
| Decibel | 39 |
| Surge protection DC | no |
| Max. efficiency (%) | 97.20 |
| Backup system light | no |
| Display | with display |
| Start input voltage (V) | 150 |
| Backup system full | no |
| Arc Fault Circuit Interrupter | no |
| Number of independent MPPT (pcs) | 3 |
| Min. temperature ambient (°C) | -10 |
| European efficiency (%) | 96.50 |
| Max. input voltage DC (V) | 1000.00 |
| Max. input current per MPPT (A). | 13 |
| Rapid shutdown | no |
| Capacity extendable later | yes without restriction |
| Max. short circuit current (A) total | 48.75 |
| Surge protection AC | no |
| Max. input current DC (A) total | 39.00 |
| Battery voltage | High Voltage |
| Max. AC power (kVA) | 8.50 |
| Battery cell chemistry | LFP |
| Max. output current (A) | 13.63 |
| MPP max. voltage range input (V) | 720.00 |
| Integrated DC switch | yes |
| Offgrid usable | no |
| Protection degree | IP55 |
| Total number of string inputs | 3 |
| Max. generator power DC (kWp) | 12.75 |
| AC nominal power (kW) | 8.50 |
| Contact ripple control receiver | yes |
| Contact for self-consumption optimization (e.g. for heat pump) | 4 |
| Usable capacity (kWh) | 8.28 |
| Shadow management | yes |
| MPP min. voltage range input (V) | 345.00 |
| Max. short circuit current per MPPT (A) | 16,25 |
| Manufacturer item name | HVM+ 8.3*PLENTICORE PLUS 8.5 G2 |
|---|---|
| Intrastat country of origin | China |
| Dangerous goods transportation category | 2 |
| Dangerous goods description | LITHIUM ION BATTERIES |
| Manufacturer | BYD + Kostal |
| Tunnel restriction code | (E) |
| Classification code | M4 |
| Intrastat product number (HS-code) | 85076000 |
| Dangerous goods class | 9 |
| Dangerous goods packaging type | 4G |
| UN No. | 3480 |
| Dangerous goods Weight (net) (kg) | 123.900 |
| Weight incl. packaging (Kg) | 170.360 |
|---|
| Weight without packaging (kg) | 156.960 |
|---|