Product information "ESS-Trene, liquid cooled"

The manufacturer's specifications regarding installation location, assembly, installation, fire protection, safety distances, etc. must be checked and confirmed in advance by the customer.

Please check for the entire system (existing + new) whether additional loggers or EMS from third-party providers are required for the required interfaces.

Commissioning must take place promptly after installation. Additional measures resulting from longer storage or downtimes are to be borne by the customer.

Suitable lifting and transport equipment must be provided by the customer. The passability of transport routes and passageways must be checked in advance.


Rarely has a storage system come as close to the term “power cube” as the new Solax Trene. The new 314 Ah standard storage cell enables a capacity of 1044 kWh with minimal space requirements. In addition to the proven liquid cooling system, the cube-shaped 10-foot container contains an inverter with 249 to 500 kVA for feeding into the 400 V low-voltage level. Real-time monitoring and a comprehensive safety concept with an aerosol fire suppression system are just a few of the impressive features. Up to 5 units can be cascaded to implement a wide variety of application scenarios.

Product advantages:
Ideal for large C&I applications
Up to 5 units can be cascaded
Comprehensive monitoring and fire protection concept
Integrated EMS1000 logger
Efficient liquid cooling system

Product features:
AC rated power: 500.0 kW
Feed-in phases: 3
AC mains voltage: 400 V
Overvoltage protection: AC type 2
Battery capacity (usable): 1044 kWh
Cell chemistry: LFP
Interfaces: Ethernet
Protection class: IP55
Cooling: Liquid cooling
Dimensions: 2991 x 2896 x 2438 mm
Weight: Total 13,000 kg

Wichtige technische Daten

Dangerous goods transportation category 2
UN No. 3536
Tunnel restriction code (E)
Classification code M4
Dangerous goods description LITHIUM BATTERIES INSTALLED IN CARGO TRANSPORT UNIT
Dangerous goods class 9
Dangerous goods packaging type 4G
Dangerous goods Weight (net) (kg) 5896.800

Technical details

Topology transformerless
Smart Home yes with supply
Max. AC power (kVA) 500.00
Max. nominal charging power (kW) 500.00
Usable capacity (kWh) 991.00
Display with display
Max. output current (A) 724.80
Contact for self-consumption optimization (e.g. for heat pump) no
Surge protection AC type 2
Commercial system yes
Max. discharging power (kW) 500.00
Cell chemistry LFP
Battery voltage High Voltage
Battery cell chemistry LFP
Integrated DC switch yes
AC nominal power (kW) 500.00
Min. temperature ambient (°C) -30
Protection degree IP55
Grid protection yes
Backup system full yes
Intrastat country of origin China
Manufacturer item name TRENE - P500B1044L-2H
Dangerous goods transportation category 2
Manufacturer SolaX Power
UN No. 3536
Tunnel restriction code (E)
Classification code M4
Intrastat product number (HS-code) 85076000
Dangerous goods description LITHIUM BATTERIES INSTALLED IN CARGO TRANSPORT UNIT
Dangerous goods class 9
Dangerous goods packaging type 4G
Dangerous goods Weight (net) (kg) 5896.800
Weight incl. packaging (Kg) 13080.000
Length incl. packaging (cm) 249.00
Amount per Pallet 1
Height incl. packaging (cm) 295.00
Width incl. packaging (cm) 304.00
Width without packaging (mm) 2991.00
Height without packaging (mm) 2896.00
Weight without packaging (kg) 13000.000
Length without packaging (mm) 2438.00
Warranty provider SolaX Power
Standard product warranty (yr) 5

Accessoires

0153778
UMG 604-PRO Network Analyzer Power Quality Analyser UMG 604-PRO
Request price
kontakt

Questions about the item?

Our experts are here to help you!

Are you a business customer and have a question about one of our products? Send us a message using this inquiry form. We look forward to your message and will get back to you as soon as possible.
Get in touch
{"extensions":[],"_uniqueIdentifier":null,"translated":[],"original_utm_params":[],"original_referrer":"","original_landing_page":"","current_utm_params":[],"has_persisted_source":false}