SCALESTAC 616 kWh / 400 kVA
Product information
CAUTION:
Hazardous material according to UN 3480 / Transport hazard class 9 / Packing Group II
***If backup power is desired, Intilion certifies installers for the purpose of component dimensioning for mains disconnection - this mains disconnection unit is then expected by Intilion on site***
***In this system configuration without the Intilion FLEPS fire protection concept, a maximum of 1 full charging cycle per day is permitted. If higher, this must be added as an additional option***
The commissioning service must be booked,
the installation service is an optional additional service.
Required accessories:
- Energy meter (article 0144363) with suitable instrument transformers
- Installation full service or installation support
As a counterpart to the outdoor-friendly Intilion Scalebloc, its big brother, the Scalestac, prefers to stay indoors. But it is the right calibre for large applications. With inverter units of 25 kVA each, up to 400 kVA output power per system can be assembled. In addition, up to 4 battery cabinets with 154 kWh energy content each are available. Depending on the system combination, charging rate and intensity of use, the Intilion fire protection concept FLEPS is partly an option or a fixed requirement.
Product advantages:
- Flexible system combinations possible
- Integrated FLEPS fire protection concept
- Integrated NA protection in accordance with VDE AR-N 4105 / 4110.
Product features:
- AC power: 400 kVA
- Mains connection: 3-phase
- Capacity (usable): 554.4 kWh
- Charge rate: 0.65 C
- Cell chemistry: LFP (lithium iron phosphate)
- Application: Peak shaving, self-consumption increase,
pre-charge storage, off-grid
- Visualisation: Intilion web server + cloud
- Protection class: IP11
- Volume: <35 dB
- Communication: Modbus TCP / IP
- Certification: VDE-AR-N 4105 + VDE-AR-N 4110
- System warranty: 10 years
- Cooling: active
- Dimensions: Control cabinet 2000 x 2310 x 800 mm (W x H x D), each
battery cabinet 1000 x 2310 x 938 mm (W x H x D)
- Weight: AC rack 400 kg, DC rack 250 kg, AC/DC rack 250-650 kg, each
Battery rack 1848.5 kg
Technical details
Storage Type: | High Voltage |
Amount connected phases: | 3 |
AC nominal power (kVA): | 400,00 |
Usable capacity (kWh): | 554,40 |
Dangerous goods UNNr: | 3480 |
Intrastat Product number: | 85076000 |
Battery Connection: | AC |
Manufacturer: | INTILION |
Manufacturer Item Name: | SCALESTAC 616 kWh / 400 kVA |
Manufacturer part number: : | SCALESTAC 616 kWh / 400 kVA |
Weight (kg): | 8.200,000 |